RTV-coated glass insulators combine toughened glass with a hydrophobic silicone coating to support conductors and reduce pollution flashover risk.
| Item |
Value |
Picture |
| Standard |
IEC 60383 |
![]() |
|
Mechanical failing load |
160 kN |
|
|
Nominal creepage distance |
550 mm |
|
|
Standard coupling |
20R |
|
|
Power frequency withstand voltage (wet) |
50 kV |
|
|
Dry lightning impulse withstand voltage |
135 kV |
|
|
Power frequency puncture voltage |
130 kV |
|
|
Radio interference voltage (10 kV, 1 MHz) |
50 μV |
|
| Colors | red/grey | |
| Brand | Nooa Electric |
1.Industrial Areas with Airborne Contaminants
RTV-coated insulators are used on overhead lines near cement plants, power stations and other industrial facilities where dust and airborne deposits can become conductive when wet. The silicone coating improves pollution flashover resistance while the glass body and metal fittings provide insulation and mechanical support.
2.Coastal and High-Humidity Transmission Lines
Salt deposits and moisture can form conductive paths across an insulator surface. For coastal projects requiring a weather-resistant glass insulator, RTV silicone provides a water-repellent surface that helps limit leakage current during salt fog, mist and condensation.
Q1. What is a 160 kN RTV-coated glass disc insulator?
A 160 kN RTV-coated glass disc insulator is a toughened glass suspension insulator with a room-temperature-vulcanizing silicone rubber coating, designed for overhead transmission lines requiring a rated mechanical failing load of 160 kN.
Q2. What does RTV mean in RTV-coated glass insulators?
RTV stands for Room Temperature Vulcanizing. It refers to silicone rubber materials that cure at room temperature to form a protective, hydrophobic coating on the glass surface.
Q3. What are the advantages of RTV-coated glass insulators?
RTV-coated glass insulators provide hydrophobic surface properties, helping reduce water film formation, leakage current, and pollution-related flashover risks in contaminated environments.
Q4. What is the difference between fully coated and partially coated RTV glass insulators?
Fully coated insulators have RTV silicone rubber applied over the entire specified glass surface, while partially coated insulators have coating applied only to designated areas.
Who We Are?
Nooa Electric Co., Ltd. - Chinese professional electrical glass insulators manufacturer with 21+ experience, covering an area of 70,000 square meters, and construction area is 50,000 square meters. There are more than 200 employees, including 25 technicians. The production capacity 3500000 pieces per year, and now setting up the new kiln and lines up to 10500000 pieces per year. We have been specialized in research and development of latest high-strength functional glass and power transmission insulators, which is the qualified supplier for State Grid Corporation of China and Southern State Grid Corporation of China, and is a participating unit of product standard formulation of the national electrical insulator standard committee.
Certificates & Reports: INTERTK, SGS, BV Certificates,Type Test Certificate.
Main Electric Insulators : Standard-type glass insulator (u40(ctv175)/u70(ctv254, ps70e)/u120/u160/u210/u300) , antipollution-type glass insulators (u120bp/u160bsp/u210bp), aerodynamic type glass electrical insulators (ug70bsa/u100bsa/u120bla), multi-umbrella type electric insulators, ground-wires type glass power line insulators (u70cn/u100cn/u120c), post insulator for line, pin glass insulator. Products are mainly used for transmission line insulation, suspension, support, tension conductors. They are divided into 5 major series: The standard type glass insulator 40-550kn, filth-resistant type glass insulators 70-420kn, aerodynamic type glass electrical insulators 120-300kn, multi-umbrella type electric insulators 120-300kn, and ground circuit type high voltage insulators, able to be used for line voltage from 10kv~1000kv.
Core Technology:
Automation Equipment: Siemens fully automatic feeding, stamping, temperature equalization, tempering, hot and cold shock control system.
Independent Product Model: U160BP/146/380/450, U160BP/155/380/450, U210BP/170/420/550 and U300BP/195/420/550.
Advanced Klin: Germany's new generation kiln control system, equipped with brand-new sensors and actuators, and equipped with a high-precision automatic batching system.
Qualification: Passed the quality, environment and occupational health system certification and obtained a number of invention patents.
Goal: